8.3.6 Disinfection
Disinfection of water is generally used either alone or as the final step in water treatment, after clarification or filtration. Disinfection is widely used to prevent the passage of bacteria, viruses and some protozoa into the distribution system. Typical chemicals used for disinfection of drinking water supplies are strong oxidants, such as chlorine (and its derivatives, chlorine dioxide and chloramine), ozone and hydrogen peroxide.
The efficiency of disinfection depends greatly on the quality of the source or treated water, and can also be strongly affected by conditions such as chemical contact time, the pH and turbidity of the water, and organic content of the water.
The aim of treatment processes used before disinfection should be to produce water with the lowest possible turbidity and organic content. Excessive particulate matter in the water can protect microorganisms from the action of disinfection chemicals. Also, excess organic matter and other oxidisable compounds in water can react with disinfection chemicals intended to inactivate microorganisms and can result in an increase in the formation of disinfection by-products (see Section 6.3.2 for general information on disinfection by-products, and the fact sheets in Section V for information on specific by-products). Best practice operation of a conventional water treatment plant should be able to produce treated water with a turbidity of less than 0.1 nephelometric turbidity units (NTU).
Last updated