Page cover

9.8 Validation of barrier performance

Typically, validation monitoring is required where new treatment processes or significant operational changes are being implemented. In particular, validation monitoring provides assurance that, where health-based assumptions are made (e.g. that the barrier will adequately remove Cryptosporidium), that these assumptions are justifiable (see Section 3.9.2).

Validation monitoring involves identifying the operational requirements that should be used to ensure that processes reduce risk to an acceptable level on an ongoing basis. In some cases, validation can be completed entirely using desktop assessment based on existing evidence; in other cases, objective empirical evidence from monitoring is needed. Validation monitoring may form part of the validation evidence base, but the precise nature of the evidence required depends on the nature of the process being validated.

One of the most common applications of in situ validation monitoring is during or just after commissioning of new unit processes. Once the process is considered to be operating as intended, but before it is brought on line to supply water to consumers, microbial and/or chemical characteristics should be assessed in samples taken before, during or after the unit process to confirm that it can reduce the concentration of substances to the extent required.

Many drinking water treatment plant manufacturers, or suppliers of treatment processes, will undertake such tests on modular units and then market those units as being pre-validated. This is commonly true for membrane and ultraviolet treatment systems. Where a pre-validated unit or system is used, then separate validation of the unit is not considered necessary, providing the validation is appropriate for the characteristics of the water to be treated.

Some examples of where validation monitoring should be undertaken include:

  • monitoring cyanotoxin concentrations pre and post a powdered activated carbon dosing system, to check the toxin reduction capability of the batch supplied;

  • monitoring microbial indicator and particle count concentrations pre and post a media-based filtration plant, to check its pathogen-reduction capability;

  • monitoring arsenic concentrations pre and post an arsenic treatment plant, to check its arsenic-reduction capability.

As part of the validation process, validation should also be undertaken on control systems, such as alarm systems or systems that instigate a plant shutdown, to ensure that they are operating correctly and respond to exceedances of target criteria or control limits.

Once a unit process has been validated, ongoing monitoring of the unit is needed to ensure that it is operating correctly. This ongoing monitoring will form part of the operational monitoring program for the water supply system.

Table 9.6 gives examples of typical validation monitoring programs for a range of commonly used unit processes, as well as providing advice on the ongoing proof-of-performance testing that is part of the operational monitoring program.

Table 9.6 Examples of validation monitoring and proof-of-performance testing

Process step to be validated
Validation monitoring
Characteristics that will subsequently be used ascertain ongoing proof of performance

Media filtration plantᵃ

Establish optimal filter run times and associated operational envelope.

Establish optimal ripening periods and associated operational envelope.

Inlet and outlet microbial indicator concentrations:ᵇ

  • Monitoring should at the very least include plate count and E. coli; it would ideally include coliphage and clostridial spores; and it may include some pathogens.

  • Turbidity upstream and downstream of system

  • Pressure loss across each filter bed

  • Particle counts on outlet

  • pH and temperature

  • Coagulant dosage rate

  • Streaming current

Membrane plant (microfiltration or ultrafiltration)ᶜ

Establish operational envelope with respect to factors such as transmembrane pressure, flux and temperature.

Inlet and outlet microbial surrogate concentrations:ᵇ

  • Refer to the USEPA Membrane Filtration Guidance Manual (2005)

  • Filtrate turbidity

  • Filtrate particle counts

  • Membrane integrity testing

  • Transmembrane pressure

  • Flux

Membrane plant (reverse osmosis)

Inlet and outlet microbial surrogate concentrations:ᵃ

  • Refer to the USEPA Membrane Filtration Guidance Manual (2005)

  • Electrical conductivity and possibly total organic carbon

  • Oxidation-reduction potential

  • Flux (recovery)

Ultraviolet plantᶜ

Establish operational envelope with respect to factors such as flow, UV transmissivity and turbidity.

Inlet and outlet microbial indicator concentrations:ᵇ

  • Refer to the USEPA UV Disinfection Guidance Manual (2006)

  • Turbidity upstream of disinfection system

  • UV transmissivity

  • UV intensity and/or calculated dose

  • Flow rate to enable calculation of retention times

  • Ballast functionality, lamp power and lamp status

  • Lamp age

  • Lamp fouling

Chlorination plant

Validation of C.t*.

  • Turbidity upstream of disinfection system

  • Free chlorine, temperature and pH at downstream monitoring point that represents the total required contact time

  • Flow rate to enable calculation of contact time (C.t)

Backflow controls

Check pressure at lowest pressure parts of system on peak flow days to ensure no negative pressure events

  • Pressure measured at pump stations and tank levels at service reservoirs

ᵃ Validation testing of media filtration systems is a highly specialised and complex task.

ᵇ If inlet microbial indicator concentrations are too low to enable validation of the expected microbial reduction performance, seeding of challenge microorganisms should be required.

ᶜ The USEPA provides definitive guidance on the validation of these types of unit processes.

* Ct = a measure of free chlorine residual concentration (C) and contact time (t)